SP tm 941 how to decrypt data. Heat calculator spt941 (mod,) instruction manual

To dispatch heat meters Logic SPT941, SPT943, you must first configure the communication parameters.

Press the MENU key and hold for about 2 seconds. The main menu of the heat meter will be displayed on the screen (using the example of SPT943.2), the cursor is placed under the GEN section:

Press the ↓ key to enter the General section of the menu, and then the -> key to move the cursor under the DB (database) section.

Press the ↓ key to enter the database, after which the screen will display the first of the section parameters and its value (EI=0):

Press the ↓ key several times until the NT option appears on the screen ( network address device).

If the facility uses one heat meter and it is not connected via a network with other Logic meters, we recommend setting the parameter value equal to one. (To change a parameter, press the ENTER key, then press the key to set the desired value, and press ENTER again to save.)

Now use the ↓ key to go to the next section parameter, CI (data interface configuration):

The value CI =0 is set by default and indicates connection communication equipment to the computer at a speed of 2400 bps. If you use a GSM modem to transfer data from the computer, we recommend setting this value and setting up the equipment and software on the dispatcher’s computer side accordingly. Firstly, it significantly saves the battery life of the computer. Secondly, in the case of unstable GSM communications, and the absence of external requests special form within 10 seconds, the computer will automatically set the parameter value equal to zero(2400 bps).

The setup of the heat meter is now complete (if you are using SPT941, the setup will be identical, with the only difference being that in the main menu of the device you first need to select the SETUP section, and then the DB section). Let's move on to connecting to the dispatch system. We recommend using (Fargo Maestro 100 or iRZ Q24) as a data transfer device.

A “smart” GSM modem does not require receiving staticIP addresses from the mobile operator, excludesfreezingGSM channel and module. Afterpower supplymodem automaticallywill come outto the network, will provide a transparent data transmission channel with a meter,and will becontrolconnection quality, rebooting if necessary.

Let's prepare a “smart” GSM modem for working with SPT941/943. Using, run the MtCfg utility from NPO Teplovizor and carry out necessary actions. After specifying all required parameters connection to the dispatch system, configure the modem port to connect to SPT941/943.

To do this, select the menu item Modem->UART Settings…

set the following values:


and press the button Save settings. Don't forget to check the box next to " Save settings in non-volatile memory«.

Now all devices are ready for operation, you need to perform physical connection. Unfasten the cover of the device to gain access to the terminals:



The RS-232 communication port we are interested in is located on connector X2:

Connect the MT9 modem and the heat meter in accordance with this diagram (the colors of the connecting lines in the diagram are arbitrary and do not match the colors of the conductors in the modem cable):

Sometimes it may be necessary to directly connect a laptop to a heat meter (service tasks, changing the device configuration, local data acquisition, etc. on-site work).

Group of companies (GK) "Teplopribor" (Teplopribory, Prompribor, Heat control, etc.)- these are instruments and automation for measuring, monitoring and regulating the parameters of technological processes (flow metering, heat control, heat metering, control of pressure, level, properties and concentration, etc.).

At the manufacturer's price, products are shipped as own production, as well as our partners - leading factories - manufacturers of instrumentation and automation equipment, control equipment, systems and equipment for control technological processes— Process control system (much is available in stock or can be manufactured and shipped in the shortest possible time).

SPT-941.20 heat calculator

Additional equipment for flow metering units (FMU) and thermal energy metering units (UUTE):
A) Pipeline accessories: installation and shut-off valves: taps, valves, gate valves, connecting fittings, tees, drains; protective coarse mesh filters, mud filters, etc. - see add. equipment and fittings for flow control devices.
b) Assembly cabinets, instrument panels, frames and racks.
V) instrumentation and automation: calculators, pressure gauges, thermometers, thermomanometers, relay sensors, alarms, temperature (thermal converters) and pressure transducers, regulators, power units (sources), control units and other devices and automation units.
G) Equipment and systems for remote dispatching
- Peripheral devices for data collection and transmission:
output modules (standard output signals, interfaces), radio modules, hubs, GSM/GPRS modems, antennas, ADF data transfer adapters, supervisory drives for collecting data from TC^, communicators, converters, interface converters (RS232/RS485/USB), indicators , computer-recorders, archivers, logic controllers, access and control panels, signal simulators, printers, lightning protection devices and other equipment.
- Software(programs for dispatch accounting, data reading systems, exchange protocols, configuration drivers and Maintenance devices and other software).
- Cable and installation wires(kits for power supply, signaling and communication (signal transmission).

At the consumer's request, the following documents can be sent:: order card (form) (questionnaire) for a universal calculator of thermal energy/quantity of heat, certificate/certificate of approval of the type of measuring instrument, permits for use, declaration of conformity, passport of the heat calculator, technical description and instruction manual, user manual for extra. equipment and peripherals, description of the type of measuring instrument and verification methodology, as well as other permits and regulatory documents (GOSTs, SanPiN, SNiPs and accounting rules, etc.).

We will be glad if the above information was useful to you, and we also thank you in advance for contacting any of the representative offices of the Teplopribor group of companies (three Teplopribor, Teplokontrol, Prompribor and other enterprises) and promise to make every effort to justify your trust.

Heat calculator SPT 941 .20 complies with GOST R EN 1434-1-2011, GOST R 51649-2000, MI 2412-97, GSSSD 187-99, TR TS 004/2011 and TR TS 020/2011.

  • Support for eleven accounting schemes.
  • Connectable sensors:
    • 3 flow transmitters with pulse output frequency up to 1000 Hz,
    • 3 pressure transducers with 4 - 20 mA output signal,
    • 3 temperature converters with characteristics 100P, Pt100, 100M.
  • Archiving of average and total values ​​of measured and calculated parameters with reference to the calculated day and hour.
  • Archiving changes to the configuration database.
  • Archiving of emergency situations and diagnostic messages.
  • 16 independent event counters and timers with customizable processing algorithms.
  • 3 communication ports: standard RS232, galvanically isolated RS232-compatible and optical, allowing simultaneous data exchange with several devices.
  • Work with GSM/GPRS/3G modems for data transmission via the Internet with support for authorization and encryption mechanisms.
  • Two discrete inputs for registration external events(control of “empty pipe”, “reverse” situations, lack of power supply to sensors, etc.).
  • Formation of a two-position output signal based on the results of event monitoring.
  • Bright and contrasting graphic OLED display.

METROLOGICAL CHARACTERISTICS

Limits of permissible error under operating conditions:

  • ± 0.01% - measurement of the frequency of pulse signals corresponding to the volumetric flow rate (relative);
  • ± 0.1% - measurement of current signals corresponding to pressure (reduced to the measurement range);
  • ± 0.1 °C - measurement of resistance signals corresponding to temperature (absolute);
  • ± 0.03 °C - measurement of the difference in resistance signals corresponding to the temperature difference (absolute);
  • ± 0.01% - clock error (relative);
  • ± 0.02% - calculation of thermal energy, mass, mass flow, volume, average temperature values, temperature difference and pressure (relative)
  • ± (0.5+3/ΔТ)% - calculation of thermal energy based on measurement results input signals(relative).

PERFORMANCE INDICATORS

Power supply: built-in 3.6 V battery (can be replaced without dismantling the device) and/or external 12 V direct current.

Weight: no more than 0.8 kg.

Dimensions: 180x194x64 mm.

Calibration interval: 4 years

Guarantee: 5 years

Terms of Use:

  • Ambient air temperature: minus 10 to plus 50 °C;
  • relative humidity: no more than 95% at 35 °C without condensation.
  • atmospheric pressure: from 84 to 106.7 kPa.

Mean time between failures: 75000 h.

Average service life: 12 years old.

Mobile application "STORAGE"

The application is used to read archived data from energy metering devices and transfer this data to a computer for further preparation of energy consumption reports.

Reading of archives of heat calculators and correctors manufactured by LOGIKA and having an optical port is provided. Read archives are stored as files. Files can be transferred to a computer by anyone in a convenient way (direct connection, Email, Bluetooth, etc.) and further processed in the PROLOG program.

The program is designed for use on devices running operating Android systems version no lower than 4.0 and having a USB-HOST port supported at the level operating system.

The program has been successfully tested on the following devices: ASUS phonepad 7, ASUS Zenfone 5, LENOVO P780, HTC One M8, Samsung Galaxy SII.

OPC server "LOGIKA"

The OPC server "LOGIKA" ensures the integration of LOGIKA devices into automated systems for various purposes, supporting data exchange standards developed by the international organization OPC Foundation.

Supports OPC DA v.3.0 and OPC HDA v.1.20 standards and transmits current and archived values ​​of measured and calculated parameters to the SCADA system (or other automated system). Support for the OPC HDA standard allows you to make full use of all the capabilities of the company’s devices, including when creating automated systems commercial accounting.

Provides data exchange with single devices or with groups of devices interconnected.

Ways to access devices:

  • direct connection to the COM port of a computer;
  • via Ethernet/Internet using Ethernet/RS232/RS485 converters;
  • By local network and the Internet using the RADIUS program;
  • using branded adapters APS79, APS45;
  • via switched telephone and radiotelephone lines, including using GSM/GPRS modems.

Can work in both local and remote server. This means that client applications can access the server located either on the same computer or on other computers on the network.

A convenient server reconfiguration mechanism is provided in order to be able to switch from one group of devices to another.

Requirements for software and hardware resources for operating the OPC server "LOGIKA":

  • operating room Windows system 7 and older;
  • RAM 1 GB;
  • installation of Microsoft .NET Framework 4.

Program "CONFIGURATOR"

The CONFIGURATOR program is designed to enter settings into following models metering devices: SPG741, SPG742, SPT940, SPT941 (mod.941.10, 941.11, 941.20), SPT942, SPT943, SPT944.

Program "PROLOG"

PROLOG is a program for receiving and storing data from metering devices, as well as outputting data in the form of tables and reports in the required format.

The current version of the program supports working with the following types devices:

  • correctors SPG741 (mod.01, 02), SPG742, SPG761, SPG761 (mod.761.1, 761.2), SPG762, SPG762 (mod.762.1, 762.2), SPG763, SPG763 (mod.763.1, 763.2);
  • heat calculator SPT940, SPT941, SPT942, SPT943, SPT944, SPT961, SPT961 (mod.961.1, 961.2), SPT961M, SPT962, SPT963.

The PROLOG program provides:

  • loading data from ADS90 and ADS91 drives;
  • downloading data from devices running Android OS;
  • downloading data from metering devices with direct connection;
  • downloading data from metering devices when connected via telephone line via modem in manual mode or according to a schedule;
  • downloading data from metering devices when connected via the Internet (TCP/IP protocol);
  • downloading data from devices on the network;
  • maintaining an archive of subscribers, nodes and accounting data;
  • printing reports on energy consumption using templates;
  • export accounting data to EXCEL tables, text documents(V rtf formats and txt) and web pages;
  • receiving current data from devices and displaying them on the computer screen in real time.

Program "RADIUS"

The RADIUS program is designed for organizing scalable systems for collecting data from metering devices from LOGIKA in networks built on the basis of the TCP/IP protocol stack, including on the Internet.

Metering devices are connected to the system via ADS98 and ADS99 adapters operating in the “client” mode. The computer on which the RADIUS program is running acts as a server for connecting clients.

The RADIUS program creates a communication channel between the adapters and the control room software(PROLOG or OPC server LOGIC). The communication channel is protected using authorization and encryption algorithms.

The program requires pre-installation Microsoft package.NET Framework 4 with update KB2468871, which can be downloaded from the developer's website.

"TECHNOLOGIST" program

The TECHNOLOG program is designed to automate the testing of LOGIKA devices, which include:

  • correctors SPG742, SPG761 (mod. 761.1, 761.2), SPG762 (mod. 762.1, 762.2), SPG763 (mod. 763.1, 763.2),
  • heat calculators SPT940, SPT941 (mod. 941.10, 941.11, 941.20), SPT943, SPT944, SPT961 (mod. 961.1, 961.2), SPT962, SPT963,
  • adapters ADS97, ADS98, ADS99 and drive ADS91.

Methods for verifying devices and testing methods for compliance with technical specifications are focused on the use of the program.

CONVERT program

The CONVERT program is designed to create hourly archive files in the format required by the Energosbyt enterprise of OJSC TGC-1.

For the program to work, you must first obtain metering data from the SPT941, SPT942, SPT943, SPT961 (mod. 961.1, 961.2), SPT961M, SPT962, SPT963 devices using the PROLOG program version no lower than 3.2.0.

Software package "SPSet®"

The SPSet software package provides two-way data exchange with multifunctional devices of JSC NPF LOGIKA: heat calculator SPT961 of all models, correctors SPG761, SPG762, SPG763 of all models, adders electrical energy SPE542.

The complex includes:

  • a program that allows you to configure the data acquisition system and ensures operation with devices in operator control mode;
  • client application that provides automatic data collection;
  • DDE server.

The complex allows you to interrogate both single devices and devices connected to a network via the RS485 interface. Data exchange can be carried out via RS232, RS485 interfaces, through an optical port, as well as through telephone or cellular modems. The data received from the devices is written into text or Access files of a known structure.

Typical design of UUTE based on heat meter SPT941.20 for 2 pipelines

Typical design of UUTE based on heat meter SPT941.20 for 3 pipelines

The UUTE project is based on the SPT 941.20 heat meter for two pipelines (T1 – supply pipeline of the heating system, T2 – return pipeline of the heating system).

The metering unit is equipped with electromagnetic flow meters, pressure sensors, and temperature sensors in accordance with the requirements of the “Rules for commercial metering of thermal energy and coolant,” approved on November 18, 2013.